APPX
Appendix 1 Operations of when the MC/MCR instructions are used to control EN
117
A
Devices specified as the device part of the OUT instruction
The following describes operations of devices specified as the device part of the OUT instruction.
Ex.
A subroutine-type FB using M0 for the device part of the OUT instruction.
When "Yes" is selected for "Use MC/MCR to Control EN"
M0 is forcibly turned off ((1) in the following figure).
When "No" is selected for "Use MC/MCR to Control EN"
The current state of M0 remains unchanged ((1) in the following figure).
Sc: Scan
EN is turned off. (User operation)
The coil turns off. (CPU module operation)
Sc: Scan
EN is turned off. (User operation)
The state of coil remains unchanged. (CPU module operation)
SM400
ENO
EN
M0
END
M0
EN
(1)
Sc
M0
EN
Sc
(1)