APPX
Appendix 1 Instruction Replacement List
93
A
IVCK IVCK SM4095 is added to parameters of
instructions. Change to an
appropriate device or label.
IVDR IVDR
IVRD IVRD
IVWR IVWR
IVBWR IVBWR
IVMC IVMC
ADPRW ADPRW
PR OUT SM4095 These instructions are not supported
by MELSEC iQ-F. Therefore, it will be
replaced to OUT SM4095.
COMRD OUT SM4095
COMRDP OUT SM4095
REFF OUT SM4095 Correct the program to use REF
instruction.
REFFP OUT SM4095 Correct the program to use REFP
instruction.
DHSCT OUT SM4095 Set the high-speed comparison table
or multi-point output high-speed
comparison table in the module
parameter “High-speed I/O”.
PLSR OUT SM4095 Correct the program to use DRVI
instruction. Set the acceleration/
deceleration time specified by the
PLSR instruction operand as the
acceleration time and deceleration
time of SD.
DPLSR OUT SM4095 Correct the program to use DDRVI
instruction. Set the acceleration/
deceleration time specified by the
DPLSR instruction operand as the
acceleration time and deceleration
time of SD.
RS OUT SM4095 Correct the program to use RS2
instruction.
VRRD OUT SM4095 These instructions are not supported
by MELSEC iQ-F. Therefore, it will be
replaced to OUT SM4095.
VRRDP OUT SM4095
VRSC OUT SM4095
VRSCP OUT SM4095
ZRN OUT SM4095 Correct the program to use DSZR
instruction. Use the same device for
near-point dog signal and zero point
signal of the DSZR instruction, and
set the zero point signal count start
time to the rear end and the zero
point signal count to 1.
DZRN OUT SM4095 Correct the program to use DDSZR
instruction. Use the same device for
near-point dog signal and zero point
signal of the DDSZR instruction, and
set the zero point signal count start
time to the rear end and the zero
point signal count to 1.
HKY OUT SM4095 Create the program using the input
device (X).
DHKY OUT SM4095
TKY
OUT SM4095
DT
KY OUT SM4095
ARWS OUT SM4095
RD3A OUT SM4095 Correct the program to use FROM
instruction.
RD3AP OUT SM4095 Correct the program to use FROMP
instruction.
WR3A OUT SM4095 Correct the program to use TO
instruction.
FX3 Series MELSEC iQ-F Remarks