EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-F Series - Page 103

Mitsubishi Electric MELSEC iQ-F Series
318 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 SYSTEM CONFIGURATION
5.4 Structure of CC-Link IE TSN Class B/A Devices (CC-Link IE TSN Protocol Version 1.0 Only) and Ethernet Devices
101
5
*8 When the firmware version of the master station is "1.002" or earlier, a local station and CC-Link IE TSN Class A remote station cannot
be connected together on the end side via the industrial switch.
*9 A connection cannot be established if the total cyclic data size of all device stations on the 100Mbps device side exceeds 2K bytes. This
includes the devices with a communication speed of 100Mbps that form a boundary between the communication speed of 1Gbps and
100Mbps. ( Page 124 Calculation of the total cyclic data size)
Precautions
When an industrial switch (for CC-Link IE TSN Class B) is used, check the industrial switch (for CC-Link IE TSN Class B)
specifications on the CC-Link Partner Association website (www.cc-link.org).

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-F Series

Related product manuals