5 SYSTEM CONFIGURATION
5.5 Connection Examples
113
5
5.5 Connection Examples
Structure of CC-Link IE TSN Class B devices only
Connection of remote I/O modules and inverters (for line topology)
The following figure shows connection of master/local module + remote I/O modules + inverters (for line topology).
Device stations can be connected up to the maximum number of connectable stations specified in the CC-
Link IE TSN performance specifications.
There is no fixed orientation, such as IN and OUT, of a connection port of each station. Any ports, such as
P1 and P1, P2 and P2, and P1 and P2, can be connected each other.
Since the master station has two connection ports (P1 and P2), both the ports can be used to connect
devices. To use only one of them, specific settings are not required.
Category Connection Description Reference
Structure of CC-Link IE TSN Class
B devices only
Connection of remote I/O modules
and inverters (for line topology)
The master station and all of the device
stations are CC-Link IE TSN Class B.
Line topology
Page 113 Connection of remote I/O
modules and inverters (for line
topology)
Connection of remote I/O modules
and inverters (for star topology)
The master station and all of the device
stations are CC-Link IE TSN Class B.
Star topology
Page 114 Connection of remote I/O
modules and inverters (for star
topology)
Connection of local stations Structure of only the master station and
local stations (CC-Link IE TSN Class B)
Line topology
Page 114 Connection of local
stations
Servo amplifier (CC-Link IE TSN
Class B) connection
The master station, local station, and
servo amplifier are all CC-Link IE TSN
Class B.
Line topology
Page 115 Servo amplifier (CC-Link
IE TSN Class B) connection
Structure of CC-Link IE TSN Class
B devices and Ethernet devices
Direct connection of Ethernet devices Connection of Ethernet devices to the
structure of CC-Link IE TSN Class B
devices only
Direct connection of Ethernet devices
to CC-Link IE TSN-compatible devices
Page 116 Direct connection of
Ethernet devices
Connection of Ethernet devices to an
industrial switch
Connection of Ethernet devices to the
structure of CC-Link IE TSN Class B
devices only
Connection of Ethernet devices via an
industrial switch
Page 117 Connection of Ethernet
devices to an industrial switch
Structure of CC-Link IE TSN Class
B/A devices only
Connection of inverters (Only the
master station is CC-Link IE TSN
Class B.)
Structure of all of the device stations
being CC-Link IE TSN Class A
Page 118 Connection of inverters
(Only the master station is CC-Link
IE TSN Class B.)
Connection of remote I/O modules
and inverters
Structure of CC-Link IE TSN Class B/A
devices coexisting as device stations
Page 121 Connection of remote I/O
modules and inverters
Connection of remote I/O modules
(CC-Link IE TSN Class B) and
inverters
Connection of CC-Link IE TSN Class B
devices and CC-Link IE TSN Class A
devices separately for each connection
port of the master station
Page 122 Connection of remote I/O
modules (CC-Link IE TSN Class B)
and inverters
Structure of CC-Link IE TSN Class
B/A devices and Ethernet devices
Direct connection of Ethernet devices Connection of Ethernet devices to the
structure of CC-Link IE TSN Class B/A
devices coexisting
Page 123 Connection of Ethernet
devices
No.0: FX5-CCLGN-MS (master station)
No.1, No.2, and No.3: Remote I/O module (remote station)
No.4, No.5, and No.6:Inverter (remote station)
No.0
Class B (1Gbps)
No.1
Class B (1Gbps)
No.2
Class B (1Gbps)
No.3
Class B (1Gbps)
No.4
Class B (1Gbps)
No.5
Class B (1Gbps)
No.6
Class B (1Gbps)