6 WIRING
6.2 CC-Link IE TSN Wiring
Wiring products
The following describes the devices used for CC-Link IE TSN.
■Ethernet cable
Use Ethernet cable that meets the following standards.
Cables for CC-Link IE TSN are available from Mitsubishi Electric System & Service Co., Ltd. (Catalogs for cable are also
available.)
In addition, the connector processing of cable length is available for your preference. Please consult your local Mitsubishi
representative.
A communication error may occur due to high-frequency noise from devices other than a programmable
controller in a given connection environment. The following describes countermeasures to be taken on the
FX5-CCLGN-MS side to avoid high-frequency noise influence.
Wiring
• Use a duplex shield type cable.
• Do not bundle the cable with the main circuit or power cable or do not place it near those lines.
• Place the cable in a duct.
■Industrial switch
Use the following industrial switches.
*1 The following industrial switch (for CC-Link IE TSN Class B) is recommended.
*2 When CC-Link IE TSN Class A devices supporting the protocol version 2.0 are connected to an industrial switch (for CC-Link IE TSN
Class A), set the VLAN function of the industrial switch (for CC-Link IE TSN Class A) to "Disabled". If the VLAN function is set to
"Enabled", cyclic transmission cannot be performed with CC-Link IE TSN Class A devices that support protocol version 2.0.
An industrial switch can be used for cascade connection.
When the industrial switch is used for cascade connection, check the specifications of the industrial switch used.
• Since there are different restrictions for system configuration using an industrial switch (for CC-Link IE TSN Class B) and
system configuration using an industrial switch (for CC-Link IE TSN Class A), setting with an engineering tool is required.
( Page 64 SYSTEM CONFIGURATION)
• Do not configure a ring topology when modules are connected to an industrial switch. Doing so, all stations will fail and data
links cannot be performed.
Communication
speed
Ethernet cable Connector Type
1Gbps Category 5e or higher, straight cable (double shielded, STP) RJ45
connector
The following conditioning cables:
• IEEE 802.3 (1000BASE-T)
• ANSI/TIA/EIA-568-B (Category 5e)
100Mbps Category 5 or higher, straight cable (double shielded, STP) RJ45
connector
The following conditioning cables:
• IEEE 802.3 (100BASE-TX)
• ANSI/TIA/EIA-568-B (Category 5)
Communication
speed
Type Model (Manufacturer)
1Gbps Category 5e or higher, straight cable (double shielded, STP) SC-E5EW series (Mitsubishi Electric System & Service Co., Ltd.)
Term Description CC-Link IE TSN Class
Industrial switch (for CC-Link
IE TSN Class B)
*1
For the models and usage methods of the industrial switches, refer to the CC-Link Partner
Association website (www.cc-link.org).
CC-Link IE TSN Class B device
Industrial switch (for CC-Link
IE TSN Class A)
*2
CC-Link IE TSN Class A device
Type Model (Manufacturer) Reference
CC-Link IE TSN industrial
managed switch
NZ2MHG-TSNT (Mitsubishi Electric Corporation) CC-Link IE TSN Industrial
Managed Ethernet Switch User's
Manual