2 SPECIFICATIONS
2.3 Performance Specifications of CC-Link IE TSN
*1 The maximum number of points for all link devices may not be used simultaneously depending on the number of device stations or the
number of points and assignments of the link devices that are set in the "Network Configuration Settings" of the "Basic Settings".
*2 To connect the FX5-CCLGN-MS to the FX5UC CPU module, the FX5-CNV-IFC and FX5-C1PS-5V are required.
*3 The maximum number of connectable stations (61) includes the master station. When connecting multiple master stations, such as the
FX5-CCLGN-MS and the FX5-40/80SSC-G, which use device station parameters for the CPU module, the total number of device
stations must be less than or equal to the number of device station parameter files that can be saved in the CPU module.
For details on the number of device station parameter files that can be saved in the FX5 CPU module, refer to the following.
MELSEC iQ-F FX5 User's Manual (Application)
*4 This setting can be used for the firmware version "1.010" or later.
*5 Even for a firmware version "1.010" or later of the FX5-CCLGN-MS, when the CC-Link IE TSN Protocol version of the remote station is
1.0, the FX5-CCLGN-MS may operate with the CC-Link IE TSN Protocol version 1.0.
*6 Use the latest version of the engineering tool.
For the latest GX Works3, please consult your local Mitsubishi Electric representative.
CC-Link IE TSN Protocol version 2.0
*4*5
•1.0
Maximum number of
connectable stations
When used as a master station 61
*3
When used as a local station 121
Station-based data assurance When used as a master station 61
*3
When used as a local station 121
Communication cable Ethernet cable which satisfies standard: ( Page 128 Ethernet cable)
Overall cable distance Line topology 12000m (when 121 stations are connected)
Others Depends on the system configuration.
Maximum station-to-station distance 100m
Network number setting range 1 to 239
Network topology Line topology, star topology (Coexistence of line topology and star topology is also
possible.)
Communication method Time sharing method
Multicast filter Supported
Transient transmission capacity 1920 bytes
Number of occupied I/O points 8 points
Applicable CPU module FX5UJ CPU module (Version 1.040 or later)
FX5U CPU module (Version 1.210 or later)
FX5UC CPU module
*2
(Version 1.210 or later)
Applicable engineering tool
*6
GX Works3 version 1.090U or later (for FX5UJ CPU module)
GX Works3 version 1.065T or later (for FX5U CPU module)