248
APPX
Appendix 2 Standard Compliant Model
Precautions for compliance with EU Directive
Precautions when using the FX5-CCLGN-MS
When using the FX5-CCLGN-MS, attach ferrite cores with the power supplies of the CPU module and the FX5-CCLGN-MS.
Attach the ferrite core with each cable wrapped around it three times at a location within approximately 200mm from the
terminal block of the power cable and connector. (Ferrite core used for testing by Mitsubishi Electric: E04SR401938
manufactured by SEIWA ELECTRIC MFG. CO., LTD.)
Precautions when using an Ethernet port
Use a double shielded twisted pair cable as the 1000BASE-T cable. Strip a part of the jacket of the shielded twisted pair cable
as shown below and ground both ends of the cable with the exposed shield to the largest area.
Power source of 24VDC power supply voltage
Supply power to the 24VDC power supply voltage of the FX5-CCLGN-MS from the AC/DC power supply installed in the same
control panel. (AC/DC power supply used for testing by Mitsubishi Electric: PS5R-VE24 manufactured by IDEC
CORPORATION.)
Compliance with UKCA marking
The requirements for compliance with UKCA marking are the same as that with EU directive (CE marking).
ShieldShield
Clamp metal fitting
Clamp metal fitting