APPX
Appendix 6 Processing Time
299
A
Multicast mode (100Mbps)
Calculation formula
Communication cycle interval [ns] =
c
+
p
. Round up values of
c
and
p
that are less than 1s.
Cyclic transmission time [ns] =
c
•
c
: This value varies depending on whether a CC-Link IE TSN Class A device station with the basic period or normal speed
period exists or not.
For details on the maximum response time for the time managed polling method of a device station, refer to
the user's manual for the device station used.
Cyclic processing time [ns] =
p
or 340000, whichever is larger. Round up values that are less than 1s.
•
p
: Cyclic processing time [ns] is calculated by p1 + p4. Round up values that are less than 1s.
Variable
For each variable (excluding Mg) to be used, round it up to one decimal point before assigning to the calculation formula.
The parts enclosed in double quotation marks (" ") in the description are the setting values for "Network Configuration
Settings".
Item Calculation formula
When a CC-Link IE TSN Class A device station with the basic period or
normal speed period does not exist
(The value in No.1 or No.4, whichever is larger) + No.5
When a CC-Link IE TSN Class A device station with the basic period or
normal speed period exists
(The value in No.1 or No.4, whichever is larger) + No.5 + No.6
Calculation formula
No.1 A1 + A2 + (No.3 or
No.4, whichever is
larger)
Calculation formula for main module A1: {(42 (n1r + n1l)) + (16 (n2r + n2l)) + (ndmr + ndml)} 80 + (Sn - 1) 5150
+ 14000 + nh
Calculation formula for extension module A2: {(42 en1r) + (16 en2r) + endmr} 80
No.2 B1+B2 Calculation formula for main module B1: {(42 n3) + (20 n4) + nds} 80 + 14000 + nh
Calculation formula for extension module B2: {(42 en3) + (20 en4) + ends} 80
No.3 C1+C2 Calculation formula for main module C1: {(42 n5) + (20 n6) + ndl} 80 + (Sn - 1) 5150 + 14000 + nh
Calculation formula for extension module C2: {(42 en5) + (20 en6) + endl} 80
No.4 50000
No.5 Dn7
No.6 Largest value of the maximum response times for the time-managed polling method for CC-Link IE TSN Class A device stations with the basic
period or normal speed period set
Name of variable Description
n1r Value of (ndmr + (16 n2r))/1488 rounded up to the nearest integer or Rn, whichever is larger
n1l Round up the calculated value to the nearest integer of (ndml+(16 n2l))/1488
n2r Rn (RYrb + RWwrb)
RYrb: Value of (Total number of points of "RY Setting" set in the remote station (main modules))/(11776 Rn) rounded up to the
nearest integer
RWwrb: Value of (Total number of points of "RWw Setting" set in the remote station (main modules))/(736 Rn) rounded up to the
nearest integer
n2l RYlb+RWwlb+1
RYlb: Value of (Total number of points of "RY setting"
*2
)/11776 rounded up to the nearest integer
RWwlb: Value of (Total number of points of "RWw setting"
*2
)/736 rounded up to the nearest integer
ndmr ((Total number of points of "RY Setting" set in the remote station (main modules))/8) + ((Total number of points of "RWw Setting"
set in the remote station (main modules)) 2)
ndml ((Total number of points of "RY setting"
*2
)/8) + ((Total number of points of "RWw setting"
*2
) 2) + 24
Sn Number of device stations
Rn Number of remote stations
Ln Number of local stations
nh Industrial switch delay time Number of industrial switches connected to the network
Industrial switch delay time: 160000
*1
n3 Sn nhs
nhs: Value of (nds + (20 n4))/(1488 Sn) rounded up to the nearest integer