62
4 FUNCTIONS
4.7 Others
4.7 Others
Device station parameter automatic setting
This function saves parameters of the device station in the master station, and automatically sets the parameters when the
device station is connected or returned to the network.
When the parameters are changed on the device station side, the saved parameters on the master station side are
automatically updated.
Device station parameter automatic setting from the master station
1. Parameters of the device station set using the engineering tool are saved in the memory of the FX5 CPU module in the
master station or the SD memory card by writing.
2. When the device station is connected or returned to the network by power-on, saved parameters are automatically set
from the master station.
The master station starts data link with the device station after parameters of the device station are
automatically set.
The device station parameter automatic setting is also executed for device stations set as reserved stations.
Automatic update of saved parameters
1. When the parameters of the device station are changed by the engineering tool or SLMP, the parameters of the device
station saved in the memory or SD memory card of the CPU module are automatically updated.
2. When a module of the device station is replaced, the master station automatically sets the updated parameters by
resetting the master station or powering off and on the system.
Parameter automatic setting of the device station can be performed under the following conditions:
The CC-Link IE TSN module on the device station. (For information on whether automatic update of saved
parameters is supported, refer to the manual for the module used for the device station.)
Save parameter (A) of the device station to the FX5 CPU module in the master station.
When the device station is returned/connected, saved parameter (A) is automatically set from the master station to the device station.
The parameters (A) of the device station are changed to (B) by SLMP or other methods.
The saved parameters (A) of the CPU module of the master station are automatically updated to the parameters (B).
No.0
No.2
ÒÓ
(A) (A)
No.0
No.2
Õ
(B)
Ô
SLMP