5 SYSTEM CONFIGURATION
5.1 Structure of CC-Link IE TSN Class B Devices and Ethernet Devices
71
5
Structure with modules on CC-Link IE TSN only
Connection with modules on CC-Link IE TSN only
Line topology
The network is configured in a line topology. An industrial switch (for CC-Link IE TSN Class B) is not required.
When an error occurs in a device station, the stations connected after the faulty station will be disconnected.
Star topology
The network is configured in a star topology via an industrial switch (for CC-Link IE TSN Class B). This allows devices to be
added easily.
Even when an error occurs in a device station, a data link can be continued with the stations that are operating normally.
Coexistence of line and star topologies
Line and star topologies can be mixed in the same network configuration.
No.0: Master station
No.1, No.2: Local station
No.3, No.4: Remote station
No.0: Master station
No.1: Local station
No.2: Remote station
No.0: Master station
No.1, No.2: Local station
No.3, No.4: Remote station
No.0 No.1 No.2
No.3 No.4
No.0 No.1
No.2
Industrial switch (for CC-Link IE TSN Class B)
No.0
No.3
No.1 No.2
No.4
Industrial switch (for CC-Link IE TSN Class B)