Loading...
760
APPX
Appendix 1 Error Codes
3E60H Safety mutual
monitoring error
SIL2 Process CPU, SIL2 function
module
A hardware failure has been
detected in the mutual monitoring
between the SIL2 Process CPU
and SIL2 function module.
Safety CPU, safety function
module
A hardware failure has been
detected in the mutual monitoring
between the Safety CPU and
safety function module.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Failure
information
At power-on,
at RESET, at
interrupt
occurrence
3E61H Always
3E68H Hardware failure A hardware failure has been
detected.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module.
Please consult your local Mitsubishi
representative.
Failure
information
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing