APPX
Appendix 1 Error Codes
773
A
4272H Debug related
function error
The trigger logging specifying the device as a trigger
condition is being performed (data logging status: RUN
waiting (no collection), Condition waiting (no collection),
Start waiting (no collection), Pause, Collecting, Trigger
waiting (collecting before trigger), Collecting after trigger, or
Saving the logging data).
Change the trigger condition. Or, stop the trigger logging
being performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start waiting
(no collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data), and register another trigger logging.
When CPU Module Logging Configuration Tool is used
Change the trigger condition. Or, stop the trigger logging
being performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start waiting
(no collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data), and start another trigger logging.
4275H Debug related
function error
Auto logging is being performed. After the auto logging, replace the SD memory card and
execute again.
4276H Debug related
function error
The function that cannot be executed during the data
logging (data logging status: RUN waiting (no collection),
Condition waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data) was executed.
Stop the data logging, and then execute the function.
4277H Debug related
function error
The number of saved files exceeded the specified number.
When CPU Module Logging Configuration Tool is used
The data logging was started in a state where the number of
saved files has exceeded the specified number. (The
operation when the number of saved files exceeded is set to
"Stop".) Or, the data logging was started in a state where the
number of saved files has exceeded the specified number.
(The operation when the number of saved files exceeded is
set to "Overwrite".)
The number of files saved in the storage destination memory
has exceeded the setting value. Delete files, or change the
storage destination and then register.
When CPU Module Logging Configuration Tool is used
The number of files saved in the storage destination memory
has exceeded the setting value. Delete files or change the
storage destination, and then start the data logging.
4278H Debug related
function error
An attempt was made to register data logging in a state
where the saved file number has reached its maximum,
FFFFFFFF. Or, the number reached to the maximum during
the execution.
When CPU Module Logging Configuration Tool is used
The data logging was started in a state where the saved file
number has reached its maximum, FFFFFFFF. Or, the
number reached to the maximum during the execution.
The saved file number in the storage target memory has
reached its maximum, FFFFFFFF. Delete files, or change
the storage destination and then register.
When CPU Module Logging Configuration Tool is used
The saved file number in the storage target memory has
reached its maximum, FFFFFFFF. Delete files or change the
storage target memory, and then perform the data logging.
427AH Debug related
function error
The common setting file is corrupted.
When CPU Module Logging Configuration Tool is used
The data logging was started to the memory where the
corrupted common setting file exists.
Write the common settings to the target memory again.
When CPU Module Logging Configuration Tool is used
Write the common settings to the target memory again.
427BH Debug related
function error
The data logging with the same file storage destination is
being performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start waiting
(no collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data).
When CPU Module Logging Configuration Tool is used
The data logging with the same file storage destination is
being performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start waiting
(no collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data).
Stop the data logging destined for the same storage, and
then register. Or, change the storage destination of the file,
and then register.
When CPU Module Logging Configuration Tool is used
Stop the data logging destined for the same storage, and
then perform another data logging. Or, change the storage
destination of the file, and then register.
4280H Debug related
function error
A file transfer test was executed from another CPU Module
Logging Configuration Tool during execution of a file transfer
test.
Execute the file transfer test again after the ongoing test is
completed.
4
282H Debug related
function error
The registration was performed with the internal buffer
capacity set to 0.
Check and correct the internal buffer capacity setting.
4283H Debug related
function error
An attempt was made to register trigger logging in a state
that the specified number of records before trigger has
exceeded the number of records that can be collected within
the internal buffer capacity.
Check and correct the internal buffer capacity setting.
Reduce the number of records before trigger.
4284H Debug related
function error
The error codes registered for memory dump are incorrect. Check and correct the error codes.
Error
code
Error name Error details and cause Action

Table of Contents