APPX
Appendix 1 Error Codes
4285H Debug related
function error
A non-executable function has been executed during
collection or save in memory dump.
Execute the function again after the completion of save in
memory dump.
4286H Debug related
function error
An item that cannot be set in the Safety CPU is specified in
the data logging settings.
Correct the data logging settings.
4287H Debug related
function error
A safety program is specified in the trigger logging step No.
specification.
Ensure that no safety program is specified in the trigger
logging step No. specification.
4288H Debug related
function error
The request cannot be executed because the number of
characters used in the name of the specified file exceeded
its limit.
Rename the file within 61 one-byte characters (including
underscore, serial number (8 digits), period, and extension),
and execute the request again.
4289H Debug related
function error
Items that cannot be set as data collection conditions are
set.
Check and correct the data collection condition setting.
428AH Data logging
function error
The data logging was started during the file batch online
change.
Start the data logging after the completion of the file batch
online change.
428CH Data logging
function error
Execution fails because any of the following files does not
exist.
CPU parameter file
Global label setting file
Program file with the target program name
Write the following files to the CPU module.
CPU parameter file
Global label setting file
Program file with the target program name
4290H Data logging
function error
The program file or global label setting file was changed
during the realtime monitor where a label (global label or
local label) is specified as a monitor target, timing condition,
or trigger condition.
Do not change the program file or global label setting file
during the realtime monitor where a label (global label or
local label) is specified.
Stop the realtime monitor where a label (global label or local
label) is specified.
Check and correct the setting of the special register
(SD940), and execute the function again.
4291H Debug related
function error
Online program change has been executed during the
execution of the real-time monitor where a step number is
specified as "Timing" or "Trigger condition".
After the completion of the online program change, check
the step number specified and execute real-time monitor
again.
4292H Debug related
function error
Real-time monitor does not begin during the execution of
real-time monitor.
Start real-time monitor after the stop of the real-time monitor
being executed.
4293H Debug related
function error
Execution fails because the internal buffer exceeds its
maximum capacity.
Check and correct the settings of internal buffer capacity,
and then try again.
4294H Debug related
function error
Execution fails because the settings of internal buffer
capacity has been changed during the execution of functions
that consume the internal buffer.
Deactivate the functions that consume the internal buffer,
and then try again. Or, restore the internal buffer capacity to
the previous state, and then try again.
42A3H Safety related
error
The safety operation mode specification details lie outside
the range.
Change the safety operation mode again.
42A4H Safety related
error
An attempt was made to change the safety operation mode
to TEST MODE while in TEST MODE, or to change the
safety operation mode to SAFETY MODE while in SAFETY
MODE.
Check whether an attempt was made to change the current
safety operation mode to the same mode.
42A5H Safety related
error
An operation that cannot be executed in SAFETY MODE
was performed.
Change the safety operation mode to TEST MODE and
execute again.
42A7H Safety related
error
The safety operation mode cannot be changed to SAFETY
MODE.
Change the CPU module operating status to other than RUN
and execute again.
Execute again after completing writing of the safety
program, safety FB file, safety CPU parameters, safety
module parameters, safety global label setting file, and
standard/safety shared label setting file.
42A8H Safety related
error
The safety operation mode cannot be changed to TEST
MODE.
Change the safety operation mode again.
42A9H Safety related
error
A CRC error occurred during communication with the Safety
CPU.
Take measures to reduce noise, and retry data
communications.
If the same error code is displayed again, the possible cause
is a hardware failure of the applicable module. Please
consult your local Mitsubishi representative.
42B0H Communications between the CPU module and the safety
function module/SIL2 function module failed.
42B4H An error was detected in the safety mutual monitoring
between the CPU module and the safety function module/
SIL2 function module.
42B8H Safety related
error
The size of the program stored in the program memory and
the size of the program being executed differ.
Restart the Safety CPU.
If the same error code is displayed again, the possible cause
is a hardware failure of the applicable module. Please
consult your local Mitsubishi representative.