776
APPX
Appendix 1 Error Codes
4309H Security function
error (user
authentication)
The specified user name has not been registered in the CPU
module.
Register user management information in the CPU module.
Log in with a registered user name.
430CH Security function
error (user
authentication)
An unauthorized file access has been attempted by a user
with an insufficient access level.
A file was accessed by an unauthorized user (access level)
with the user authentication function enabled (file access
control enabled).
The CPU module does not support the access level of the
user.
Access files within the authorized scope.
Files should be accessed by authorized users.
Files should be accessed by users with an access level
supported by the CPU module.
430DH Security function
error (user
authentication)
An operation requiring authentication was executed from a
startup source that does not support the user authentication
function with the user authentication function enabled.
Perform the operation from a device that supports the user
authentication function.
4314H Security function
error (user
authentication)
A user authentication operation was performed with the user
authentication function disabled.
Perform the operation after enabling the user authentication
function.
4317H Security function
error (user
authentication)
An attempt was made to change the user management
information of the logged on user.
The operation should be performed after the logged on user
logs off.
4318H Security function
error (user
authentication)
An attempt was made to initialize all programmable
controller information (operation that disables user
authentication function) with a user logged on.
The operation should be performed after the logged on user
logs off.
4319H Security function
error (user
authentication)
An attempt was made to initialize all programmable
controller information (operation that disables user
authentication function) while logged on.
The operation should be performed after logging off.
431BH Security function
error (user
authentication)
An unauthorized operation has been attempted by a user
with an insufficient access level.
The CPU module does not support the access level of the
user.
Check the access level of the user.
Files should be accessed by users with an access level
supported by the CPU module.
431CH Security function
error (user
authentication)
The number of simultaneously logged on users exceeds the
maximum value, and therefore the system is unable to
authenticate the applicable user.
Unnecessary logged on users should log off.
Adjust the number of log ons to within the maximum value.
431DH Security function
error (user
authentication)
An operation that requires the authentication was performed
with no user management information registered in the CPU
module.
Register user management information in the CPU module.
433CH Maintenance
and inspection
error
The error was not cleared. (Error clear was performed
during execution of error clear.)
Execute again after a while.
If the same error code is displayed again, the possible cause is
a hardware failure of the target module. Please consult your
local Mitsubishi representative.
433DH Maintenance
and inspection
error
The target module cannot handle the error clear. Check the target module. (Check the module in which the
error occurred.)
4400H Security function
error
A file protected by a password has been opened without
unlocking the password.
Enter a correct password and perform password
authentication.
4401H Security function
error
Read password authentication has failed when required.
The file password format is incorrect.
Set a correct read password and perform password
authentication.
Access the file with the correct method.
4
402H Security function
error
Write password authentication has failed when required.
The file password format is incorrect.
Set a correct write password and perform password
authentication.
Access the file with the correct method.
4403H Security function
error
Both passwords for reading and for writing that are set upon
Create, Change, Delete, or Disable do not match the
previous ones.
Set correct passwords for both reading and writing, and
perform password authentication.
4404H Security function
error
A file error was detected before or after performing Create,
Change, or Delete.
Initialize the drive including the target file by initializing the
memory.
Write the target file to the programmable controller again,
and then register or cancel the file password.
4408H Security function
error
Password authentication failed when access was required. Set a correct password and perform password
authentication again.
4409H Security function
error
Password authentication failed when access was required. Set a correct password and perform password
authentication again 1 minute later.
440AH Security function
error
Password authentication failed when access was required. Set a correct password and perform password
authentication again 5 minutes later.
Error
code
Error name Error details and cause Action

Table of Contents

Related product manuals