784
APPX
Appendix 1 Error Codes
4C44H File transfer
function (FTP
client) error
The file transfer function (FTP client) is executed while the
following functions are being executed.
CPU module data backup/restoration function
iQ Sensor Solution data backup/restoration function
Execute the File transfer function (FTP client) again after the
mentioned function is completed.
4C50H Special relay
and special
register function
error
The free space in the data memory is not enough. Increase the free space in the target memory (data memory)
and execute the function again.
4C51H Special relay
and special
register function
error
Writing to the data memory is not completed successfully. Initialize the memory to bring the drive (data memory) back
to normal state.
4C52H Special relay
and special
register function
error
The function memory clear request or the data memory file
transfer request is sent during a data logging.
Do not send the function memory clear request or the data
memory file transfer request during a data logging.
4C53H Special relay
and special
register function
error
The function memory clear request or the data memory file
transfer request is sent during execution of the following
functions.
File batch online change
Data transfer to the data memory
Send the function memory clear request or the data memory
file transfer request after the completion of the functions.
4C54H Special relay
and special
register function
error
The request cannot be executed because the CPU module
is not in the STOP state.
Set the operating status of the CPU module to STOP, and
execute the request again.
4C55H Special relay
and special
register function
error
The number of files in the root directory and subdirectory in
the data memory exceeded the limit.
Increase the free space in the data memory and execute the
request again.
Delete files in the data memory, and execute the request
again.
4C56H Special relay
and special
register function
error
Reading from (an access to) a file is failed.
The specified file does not exist. Or, the specified
subdirectory does not exist.
Check that the file is not deleted.
Check the file name and subdirectory name. Then, execute
the function again.
C000H
to
CFBFH
MELSEC iQ-R Ethernet User's Manual (Application)
CFC0H Cyclic
transmission
error (master
station)
Unable to execute cyclic transmission because multiple
master stations exist in the same network address.
Check the existence status of master station in network.
CFC1H Cyclic
transmission
error (master
station)
Unable to execute cyclic transmission because the error
occurred in cyclic transmission.
Take measures to reduce noise.
If the same error is displayed again, please contact your
local Mitsubishi representative.
CFC8H Cyclic
transmission
error (master
station)
Unable to execute cyclic transmission because the slave
station controlled by other master station exists.
Check the existence status of master station in network.
Check the slave station where the error occurred.
CFC9H Cyclic
transmission
error (master
station)
Unable to execute cyclic transmission because the slave
station of the same IP address exists in the same network
address.
Check the existence status of slave station in network.
Check the slave station where the error occurred.
CFD0H Master station
error
The port No. (61450) used in CC-Link IE Field Network
B
asic has already been used.
Check the port No. used in Ethernet function.
CFD1H Master station
error
Invalid value has been set in subnet mask. Check the parameter setting.
CFE0H Cyclic
transmission
error (slave
station)
The cyclic transmission was executed for the slave station
controlled by other master station.
Check the existence status of master station in network.
Check the slave station where the error occurred.
CFE1H Cyclic
transmission
error (slave
station)
The unusable number of occupied stations has been
specified from master station.
Check the number of occupied stations setting in master
station parameter (Network Configuration Settings).
Check the slave station where the error occurred.
Error
code
Error name Error details and cause Action

Table of Contents