APPX
Appendix 5 List of Special Register Areas
837
A
SD81 to
SD111
Detailed
information 1
Detailed
information 1
(5) System configuration information
SD81: With or without specification
b0: I/O number
b1: Slot number
b2: Base number
b3: Power supply number
b4: CPU number
b5: Network number
b6: Station number
SD82: I/O number
SD83
b0 to b7: Slot number (0 to 11)
b8 to b15: Base number (0: Main base unit, 1 to 7: Extension base unit
level 1 to level 7, 8: Higher than level 7)
SD84
b0 to b7: Power supply number (1 to 2: Power supply 1 to 2)
b8 to b15: CPU number: (1 to 4: CPU 1 to 4)
SD85: Network number
SD86: Station number
0 to 120 (0 is stored for the master station.)
(6) Number of times information
When there is no specification, 0 is set to each SD.
SD81: With or without specification
b0: Number of times (set value)
b1: Number of times (actual measurement value)
SD82 to SD83: Number of times (set value)
SD82: Lower word of the number of times (set value)
SD83: Upper word of the number of times (set value)
SD84 to SD85: Number of times (actual measurement value)
SD84: Lower word of the number of times (actual measurement value)
SD85: Upper word of the number of times (actual measurement value)
(7) Time information
When there is no specification, 0 is set to each SD.
SD91: With or without specification
b0: Time (value set) (ms)
b1: Time (value set) (s)
b2: Time (actual measurement value) (ms)
b3: Time (actual measurement value) (s)
S (Error) ALL
No. Name Data stored Details Set by
(setting
timing)
CPU
b1b2b3b4b5b6 b0
b15 b7b8
b0
b15 b7b8
b0
b1 b0
b1b0b2b3