7 OFFSET/GAIN SETTING
7.1 Setting Procedure
37
7
7 OFFSET/GAIN SETTING
Using the user range setting requires setting the offset and gain values.
Access to the offset/gain setting window in the engineering tool to set the offset and gain values.
7.1 Setting Procedure
The setting procedure for the offset/gain setting of a temperature input module is as follows:
[Tool] [Module Tool List]
1. In "Temperature Input", select "Offset/gain setting" and
click [OK] button.
2. Select the target module for the offset/gain setting, and
click [OK] button.
3. Click [Yes] button.