APPX
Appendix 1 Error Codes
705
A
112EH Connection
establishment
failed
A connection could not be
established in the open
processing.
Continue Check the operation of the external
device.
Check if the open processing has been
performed in the external device.
Check and correct the port number of
the module, IP address/port number of
the external device, and opening
method.
When the firewall is set in the external
device, check if the access is
permitted.
Check if the Ethernet cable is
disconnected.
Always
1133H Socket
communications
response send
error
The response send failed during
socket communications.
Continue Check the operation of the external
device or switching hub.
Since there may be congestion of
packets on the line, send data after a
certain period of time.
Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Always
1134H TCP connection
timeout
A TCP ULP timeout error has
occurred in the TCP/IP
communication. (The external
device does not send an ACK
response.)
Continue Check the operation of the external
device.
Check and correct the TCP ULP
timeout value.
Since there may be congestion of
packets on the line, send data after a
certain period of time.
Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Always
1152H IP address error The IP address is not set correctly. Continue Correct the IP addresses. Parameter
information
Always
1155H Connection
number
acquisition error
The specified connection was
already closed in TCP/IP
communications.
Open processing is not
performed.
Continue Perform the open processing for the
specified connection.
Check if the open processing has been
performed in the external device.
Always
1157H Receive buffer
securement
error
The specified connection was
already closed in UDP/IP
communications.
Open processing is not
performed.
Continue Perform the open processing for the
specified connection.
Check if the open processing has been
performed in the external device.
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing