13 SERIAL COMMUNICATION MODULE DEDICATED COMMANDS
13.4 Mode Switching Function
261
13
Transmission setting
Specify the transmission setting after switching the C24 mode.
For the transmission setting, refer to the following manuals.
MELSEC iQ-R Serial Communication Module User's Manual (Application)
MELSEC-Q/L Serial Communication Module User's Manual (Application)
■Data communication in ASCII code
Convert the numerical value to 4-digit ASCII code (hexadecimal), and send it from the upper digits.
■Data communication in binary code
Send a 1-byte numerical value from lower byte (L: bits 0 to 7).
When the transmission settings are as follows:
Bit Item OFF (0) ON (1)
b0 Operation setting Independent Interlink
b1 Data bit 7 8
b2 Parity bit None Yes
b3 Odd/even parity Odd Even
b4 Stop bit 1 2
b5 Sum check code None Yes
b6 Online change Disable Enable
b7 Setting change Disable Enable
Bit Item Setting ON/OFF
b0 Operation setting Independent OFF
b1 Data bit 8 ON
b2 Parity bit Yes ON
b3 Odd/even parity Odd OFF
b4 Stop bit 1 OFF
b5 Sum check code Yes ON
b6 Online change Enable ON
b7 Setting change Enable ON
ASCII code Binary code