13 SERIAL COMMUNICATION MODULE DEDICATED COMMANDS
13.5 Programmable controller CPU monitoring function
273
13
Communication example (for fixed cycle send)
Perform the Programmable controller CPU monitoring registration with the following conditions.
• Cycle time units, cycle time: 30 seconds
• Programmable controller CPU monitoring function: Fixed cycle send
• Number of registered word blocks: 2 blocks
• Number of registered bit blocks: 1 block
• CPU error monitoring: Included
The response data indicates the following data.
(1) Word device information (1-point)
*1 The additional code is added. (Page 35 Additional code (10H))
(2) Bit device information (1-point)
(3) CPU status information
• CPU status information: Module warning occurring (0001)
Block Monitoring start device Registered points
Word device registration (1-point) D0 4 points
Word device registration (2-point) W100 8 points
Bit device registration (1-point) M0 2 points
Device data D0 D1 D2 D3
Device value Decimal 99 4144 5445 10240
Hexadecimal 0063H 1030H 1545H 2800H
ASCII code Word unit 30303633 31303330 31353435 32383030
Byte unit 36333030 33303130 34353135 30303238
Binary code Word unit 0063 101030
*1
1545 2800
Byte unit 6300 301010
*1
4515 0028
Device data M15 to M8 M7 to M0 M31 to M24 M23 to M16
Device value Bit 0 0 0 1 0 0 010011000101001 0 0001001001
Byte 11H 31H 48H 49H
Word 1131H 4849H
ASCII code Word unit 31313331 34383439
Byte unit 33313131 34393438
Binary code Word unit 1131 4849
Byte unit 3111 4948