17 COMMUNICATING USING 1C FRAMES
17.6 Read and write Buffer Memory of Special Function Module
Special function module No.
Specify the last input/output signal (I/O address) of the special function module. (Specify the upper 2-digit in 3-digit
representation.)
Convert the numerical value to 2-digit ASCII code (hexadecimal), and send it from the upper digits.
Special function module No. which occupies 1 slot
Special function module No. is the upper 2 digits of the input/output signal (I/O address) of the last number represented with 3-
digits on the slot where the module is mounted.
Special function module No. which occupies 2 slots
For a special function module which occupies two slots, the number of occupied points for each slot is fixed for each module.
Special function module No. specified for the operation procedure is the upper 2 digits of the input/output signal (I/O address)
of the last number represented with 3-digits of the slot assigned as a special function module on the slot.
For details of the assigned slot for each module, refer to the manual of the modules.
Ex.
A module that assign the first part of the slots as empty slots (AD72, A84AD, etc.)
Ex.
A module that assign the last part of the slots as empty slots (A61LS, etc.)
Ex.
A module in which both assignment of special function module and I/O assignment exist (A81CPU)
Special
function
module
Special
function
module
Power
supply
module
CPU
module
Input Output Input Output Input Output
16 points 32 points16 points 16 points 32 points 32 points32 points 32 points
Module No. "0AH"
Special
function
module
Power
supply
module
Module No. "07H"
Input Output Output Output
32 points 32 points16 points 32 points 32 points
Module No. "13H"
00 to 0F 10 to 2F 30 to 4F 50 to 5F 60 to 7F 80 to 8F 90 to AF B0 to CF
D0 to DF E0 to FF 100 to 11F 120 to 13F 140 to 15F
Special
function
module
(Empty
slot)
Module No. "02H"
16 points 32 points
00 to 0F 10 to 2F
Special
function
module
(Empty
slot)
Module No. "01H"
16 points
32 points
00 to 0F 20 to 2F
Special
function
module
Input
module
Module No. "03H"
64 points
64 points
00 to 3F 40 to 7F