6 ACCESS ROUTE SETTINGS
6.2 Details of Setting Data
57
6
Accessing multiple CPU system, redundant system
Specify the access target with the request destination module I/O No. Specify the fixed value (00H) for the station No.
*1 When executing a command that manages files, specify the I/O number other than that of the control system (03D0H) and standby
system (03D1H). Otherwise, the access target is changed and the files cannot be read/written.
Access target Request destination module I/O No. Request destination module station No.
Multiple CPU system Control CPU 03FFH 00H
Non-control
CPU
Multiple CPU No.1 03E0H
Multiple CPU No.2 03E1H
Multiple CPU No.3 03E2H
Multiple CPU No.4 03E3H
Redundant system CPU module Control system
*1
03D0H
Standby system
*1
03D1H
System A 03D2H
System B 03D3H
CC-Link IE
Field Network
remote head
module
Remote head No.1 03E0H
Remote head No.2 03E1H
Control system
*1
03D0H
Standby system
*1
03D1H