11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
1199
11
Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
Operand: (d2)
Device Symbol Name Recommended range Data type Standard
value
Set by
+1 MODE Control mode 0 to FFFFH 16-bit unsigned
binary
8H User/
system
+3 ALM Alarm detection 0 to FFFFH
SPA
0: Loop RUN
1: Loop STOP
SEA
0: No alarm
1: Alarm
16-bit unsigned
binary
0H User/
system
+4 INH Disable alarm
detection
0 to FFFFH
0: Alarm detection enabled
1: Alarm detection disabled
16-bit unsigned
binary
0H User/
system
+38
+39
Filter coefficient 0 to 1 Single-precision
real number
0.2 User
b15 b9b10 b1b2b3b4b5b6b7b8 b0
CMV
CSV
LCM
LCA
LCC
MAN
AUT
CAS
CMB
CAB
CCB
...
b15b14 b9 b0
SEA
SPA
......
b15 b9 b0
SEI
ERRI
... ...