11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
1215
11
Operation constant
Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
Processing details
This instruction performs output conversion of the manipulated value (MV) in the device specified by (d2), and stores the
result in the device specified by (d1).
The following is the processing block diagram of the S.MOUT instruction. (The numbers (1) to (3) in the diagram indicate the
order of the processing.)
Operand: (s2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
NMAX Output
conversion
upper limit
-999999 to 999999 Single-precision
real number
100.0 User
+2
+3
NMIN Output
conversion
lower limit
-999999 to 999999 Single-precision
real number
0.0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+1 MODE Control mode 0 to FFFFH 16-bit unsigned
binary
8H User/
system
+3 ALM Alarm detection 0 to FFFFH
SPA
0: Loop RUN
1: Loop STOP
16-bit unsigned
binary
4000H User/
system
+12
+13
MV Manipulated
value
-10 to 110 [%] Single-precision
real number
0.0 User
b15 b9b10 b1b2b3b4b5b6b7b8 b0
CMV
CSV
LCM
LCA
LCC
MAN
AUT
CAS
CMB
CAB
CCB
...
b15
b14
b0
...
SPA
SPA
BW
MAN
MODE
(1)
(2)
(3)
(3)
NMAX, NMIN
MV
RUN (SPA=0)
STOP (SPA=1)
Output
conversion
Loop stop
processing
BW=Last value
BW=Last value
Mode
determination
Other than MAN,
CMB, CMV, LCM
MAN, CMB,
CMV, LCM
Loop stop
determination