1228
11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
Input data
Block memory
Operation constant
Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
Operand: (s1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Input value Use a ring counter consisting of 16 bits or more.
16-bit ring counter
00000000H 0000FFFFH 00000000H[pulse]
24-bit ring counter
00000000H 00FFFFFFH 00000000H[pulse]
32-bit ring counter
00000000H FFFFFFFFH 00000000H[pulse]
However, set 32767 (7FFFH) or less for the pulse increment in
each instruction execution.
32-bit unsigned
binary
User
+2 e e1 Integration start
signal
Integration start signal
0: Integration stop/reset
1. Integration start
Integration hold signal
0: Integration hold clear
1: Integration hold
16-bit unsigned
binary
User
e2 Integration hold
signal
Operand: (d1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW1 Output value
(integral part)
0 to 2147483647 32-bit unsigned
binary
System
+2
+3
BW2 Output value
(decimal part)
0 to 2147483647
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0 W Weight per
pulse
1 to 999 16-bit unsigned
binary
1 User
+1 U Unit conversion
constant
1, 10, 100, 1000 16-bit unsigned
binary
1 User
+2
+3
HILMT Integration
upper limit
1 to 2147483647 32-bit unsigned
binary
21474836
47
User
+4 SUMPTN Integration
pattern
0: Return to 0 when the integration upper limit (HILMIT) is
exceeded.
1: Holds the integration upper limit (HILIMT) when it is
exceeded.
16-bit unsigned
binary
0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+10
+11
SUM1 Integrated value
(integral part)
0 to 2147483647 32-bit unsigned
binary
0 System
+12
+13
SUM2 Integrated value
(decimal part)
0 to 2147483647 32-bit unsigned
binary
0 System
b15 b1 b0
e1
e2
...