11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1249
11
Loop tag past value memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
The loop tag past value memory occupies 32 words after the loop tag memory.
Set value
The set value (E2) is valid only when b0 of the set value pattern (SVPTN) is set to 0 (Used). To use the upper loop MV as the
set value (E2), specify the device (offset +12) where the manipulated value (MV) of the upper loop is set.
If E2 is not used, specify a dummy device (SD820).
Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
+60
+61
GG Gap gain 0 to 999999 Single-precision
real number
1.0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+96 Control cycle
counter
initialization
completion flag
System
+97 Control cycle
counter (The
value is rounded
off to the nearest
whole number.)
+100
+101
I
n-1
Last value
+102
+103
B
n-1
Last value
+104
+105
PV
n
Process value
+106
+107
PV
n-1
Last process
value
+116 ALM2 Alarm detection
2
MHA2, MLA2
0: No alarm
1: Alarm
Operand: (s3)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E2 Set value -10 to 110 [%] Single-precision
real number
0.0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
b15 b0b1b2
MHA2
MLA2
...