11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1285
11
Engineering value inverse transformation (1)
The instruction performs the following operations to match the ranges of PH, PL, HH, and LL to the input values (E1).
Upper/lower limit check (2)
The upper and lower limits of the input value (E1) are checked under the following conditions.
*1 If ERRI or PHI of disable alarm detection (INH) is set to 1, PHA of ALM and BB2 are set to 0.
*2 If ERRI or PLI of disable alarm detection (INH) is set to 1, the PLA of ALM and BB3 are set to 0.
*3 If ERRI or HHI of disable alarm detection (INH) is set to 1, HHA of ALM is set to 0.
*4 If ERRI or LLI of disable alarm detection (INH) is set to 1, LLA of ALM is set to 0.
Variation rate check (3)
A variation rate check is performed for the duration specified by the variation rate alarm check time (CTIM). The number of
executions of a variation rate check is determined by the following expression.
Set CTIM and T so that m 2.
No processing is performed when m = 0 (integral part).
Ex.
When m = 4, operations are performed as shown below.
Check item Condition ALM BB2 BB3
Upper limit check E1 > PH' PHA = 1
*1
1
*1
E1PH' - HS PHA = 0 0
Others PHA: The last value is held.
*1
Hold
*1
Lower limit check E1 < PL' PLA = 1
*2
1
*2
E1PL' + HS PLA = 0 0
Others PLA: The last value is held.
*2
Hold
*2
Upper upper limit check E1 > HH' HHA = 1
*3

E1HH' - HS HHA = 0 
Others HHA: The last value is held.
*3

Lower lower limit check E1 < LL' LLA = 1
*4

E1LL'+HS LLA = 0 
Others LLA: The last value is held.
*4

(1) 0th time: E1
n
-E1
n-4
(2) 1st time: E1
n
-E1
n-4
(3) 2nd time: E1
n
-E1
n-4
(4) 3rd time: E1
n
-E1
n-4
(5) 4th time: E1
n+4
-E1
n
Ec: Execution cycle
PH'= ×(PH-RL)
RH-RL
100
PL'= ×(PL-RL)
RH-RL
100
HH'= ×(HH-RL)
RH-RL
100
LL'= ×(LL-RL)
RH-RL
100
m=
©T
CTIM
E1
n
E1
n+1
E1
n+2
E1
n+3
E1
n+4
(1) (2) (3) (4) (5)
CTIM
DPL
t
Ec