11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■Input data
■Block memory
■Operation constant
Operand: (s1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Input value -999999 to 999999 [%] Single-precision
real number
User/
system
Operand: (d1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 [%] Single-precision
real number
System
+2 BB BB1 Operation result
0: |BW|<50%
1: |BW|50%
16-bit unsigned
binary
System
Operand: (s2)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0 PN Operation mode 0: Reverse action
1: Direct action
16-bit unsigned
binary
0User
+1 TRK Tracking bit 0: Tracking not performed
1: Tracking performed
16-bit unsigned
binary
0User
+2 SVPTN Set value
pattern
0 to 3
(1) Use of set value
Specify whether to use the set value (E2) or not.
0: Used
1: Not used
(2) Set value pattern
Specify whether to use the upper loop MV as the set value (E2) or
not.
0: E2 is the upper loop MV.
1: E2 is not the upper loop MV.
16-bit unsigned
binary
3User