15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1463
15
Control data
Operand: (s1)
Device Item Description Setting range Set by
+0 Error completion type
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
0: Do not set data in (s1)+12 and later at completion with an error.
1: Set data in (s1)+12 and later at completion with an error.
(2) Arrival check time setting (bit 8)
0: 1s units
1: 100ms units
(3) Target station address specification method (b15)
0: Specify "network No." in (s1)+4, and "station number" in (s1)+5.
1: Specify "IP address" in (s1)+4, 5 (Ethernet only)
0000H
0080H
0100H
0180H
8000H
8080H
8100H
8180H
User
+1 Completion status The completion status is stored upon completion of the instruction.
•0: Normal
Other than 0: Error (error code)
System
+2 Own station channel Specify the channel to be used by own station. (Page 1450 Range of available
channel numbers)
1 to 18 User
+3 Target station CPU type Specify the CPU type of the target station.
0000H: Addressed to target station CPU (control CPU)
03D0H: Addressed to control system CPU
03D1H: Addressed to standby system CPU
03D2H: Addressed to system A CPU
03D3H: Addressed to system B CPU
03E0H: Addressed to multiple CPU No. 1
03E1H: Addressed to multiple CPU No. 2
03E2H: Addressed to multiple CPU No. 3
03E3H: Addressed to multiple CPU No. 4
03FFH: Addressed to target station CPU (control CPU)
0000H
03D0H to 03D3H
03E0H to 03E3H
03FFH
User
+4 Target network number [CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the network number (1 to 239) of the target station.
(s1)+4
Network No.:
1 to 239
(s1)+5
Station No.:
1 to 120, 125, 126
(s1)+4, 5
IP address:
00000001H to
FFFFFFFEH
(1 to 4294967294)
User
[Ethernet]
When "0" is specified in bit 15 of (s1)+0
Specify the network number (1 to 239) of the target station.
When "1" is specified in bit 15 of (s1)+0
Specify the IP address (third and fourth octets) of the target station.
b8 to b15: 3rd octet
b0 to b7: 4th octet
+5 Target station number [CC-Link IE Controller Network]
Specify the station number (1 to 120) of the target station.
User
[CC-Link IE Field Network]
Specify the station number of the target station.
125: Master station
126: Master operating station
1 to 120: Local station, intelligent device station, submaster station
[Ethernet]
When "0" is specified in bit 15 of (s1)+0
Specify the station number (1 to 120) of the target station.
When "1" is specified in bit 15 of (s1)+0
Specify the IP address (first and second octets) of the target station.
b8 to b15: 1st octet
b0 to b7: 2nd octet
+6 Not used 
b15
00(3)
(2) (1)
b7b8 b0
……
b15 b7b8
……
b0
b15 b7b8
……
b0