1486
15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
■Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■Control data
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B,
SB, FX, FY
J\ T, ST, C, D, W,
SD, SW, FD,
R, ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K,
H
E $ J U
(J/U) JP.SEND
GP.SEND
(s1)
*2
(s2)
*2
(d)
*1
*3
Operand: (s1)
Device Item Description Setting range Set by
+0 Execution/error
completion type
(1) Execution type (b0)
• 0: No arrival acknowledgment
When the target station is in the same network: Completed when data has been sent
from the own station.
When the target station is in another network: Completed when data has arrived the
relay station of the own network.
• 1: Arrival acknowledgment used
Completed when data has been stored in the specified channel of the target station.
(2) Error completion type (bit 7)
Specify whether to set clock data when completed with an error.
• 0: Clock data at error occurrence is not stored in (s1)+11 and later.
• 1: Clock data at error occurrence is stored in (s1)+11 and later.
0000H
0001H
0080H
0081H
User
+1 Completion status The completion status is stored upon completion of the instruction.
•0: Normal
• Other than 0: Error (error code)
System
+2 Own station channel Specify the channel to be used by own station. (Page 1450 Range of available
channel numbers)
1 to 8, 11 to 18 User
+3 Target station storage
channel
Specify the channel of the target station for storing data.
(CC-Link IE Field Network only: 1 or 2)
1 to 8 User
Completed
Target
station
Request
source
Completed
Target
station
Request
source
Relay
station
Completed
Target
station
Request
source
Relay
station
Target
station
Completed