1514
15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
■Request data
■Response data
• For details on the remote operation, refer to the user's manual for the CPU module used.
• Remote RUN/STOP is valid when the RUN/STOP key switch on the RCPU, QCPU, LCPU, or QnACPU of
the target station is set to RUN.
• Remote RUN/STOP is disabled when System Protect is applied to the CPU module of the target station.
• While another station already executes Remote STOP/PAUSE for the target station, the own station cannot
execute RUN if "Do not forcibly execute" is set in (s2)+2.
• If the RCPU, QCPU, LCPU, or QnACPU of the target station for which Remote RUN/STOP has been
executed is reset, the Remote RUN/STOP information is deleted.
• The clear mode set in (s2)+3 is used to specify the clear processing (initialization) mode of the device
memory of RCPU, QCPU, LCPU, or QnACPU when the CPU operation is started by Remote RUN. The
RCPU, QCPU, LCPU, or QnACPU performs clearing as specified and runs according to the parameter
setting (initial device value).
• The number of resends (s1)+7 must be set every time the instruction is executed.
Operand: (s2)
Device Item Description Remote
RUN
Remote
STOP
Set by
+0 Request type • 0010H: When the station number is specified by (s1)+5
• 0030H: When All Station or the group is specified by (s1)+5
User
+1 Subrequest type • 0001H: Remote RUN
• 0002H: Remote STOP
User
+2 Operation mode Specify whether to forcibly execute Remote RUN/STOP.
■Remote RUN
• 0001H: Do not forcibly execute.
• 0003H: Forcibly execute (can be specified when executing Remote RUN).
■Remote STOP
• 0003H (fixed)
(Forced execution is the function used, when the station that executed
Remote STOP can no longer executed Remote RUN, to allow another station
to forcibly execute Remote RUN.)
User
+3 Clear mode Effective only for Remote RUN. Specify whether to clear the CPU device
memory.
• 0000H: Do not clear (the local device is cleared, though).
• 0001H: Clear (excluding the latch range)
• 0002H: Clear (including the latch range)
User
Operand: (d1)
Device Item Description Remote
RUN
Remote
STOP
Set by
+0 Request type • 0090H: When the station number is specified by (s1)+5 System
+1 Subrequest type • 0001H: Remote RUN
• 0002H: Remote STOP
System