16 ETHERNET INSTRUCTIONS
16.1 Open/Close Processing Instructions
1537
16
Control data
Operand: (s2)
Device Item Description Setting range Set by
+0 Execution type/End
type
(1) Execution type
*1
Specify whether to use the parameter value set by the engineering tool or the value
set in (s2)+4 to (s2)+14 of control data for opening a connection.
0: Performs open processing according to the "external device connection
configuration" set by the engineering tool.
1: Performs open processing according to the setting in (s2)+4 to (s2)+14 of
control data.
If the CP.CONOPEN instruction is executed by setting the value for the external
device connection configuration of the engineering tool and also setting device
(s2)+0 to 1, the instruction performs open processing according to the value set in
its control data.
Even if a value is set in (s2)+4 and later after setting (s2)+0 to 0, the value is
ignored.
0000H
0100H
User
+1 Completion status The completion status is stored upon completion of the instruction.
0: Completed successfully
Other than 0: Completed with an error (error code)
System
+2 System area 
+3 System area 
+4 Application setting area Specify the application of a connection.
Fixed buffer communications
(1) Application of fixed buffer (b0)
0: For sending
1: For receiving
(2) Communication code (b1)
0: Binary code
1: ASCII code
(3) Online program change (b3)
0: Disable
1: Enable
(4) Pairing open (b4)
0: Disable pairing open.
1: Enable pairing open.
*2
(5) Communication method (protocol) (b5)
0: TCP/IP
1: UDP/IP
(6) Fixed buffer communications with/without procedure (b6 and b7)
00: With procedure
01: Without procedure
(7) Alive check (b8 and b9)
00: KeepAlive
*4
01: Alive check with UDP
*5
10: Disable the alive check.
(8) Opening method (b10 and b11)
00: Active open or UDP/IP
10: Unpassive open
11: Fullpassive open
Socket communications
(1) Online program change (b3)
0: Disable
1: Enable
(2) Communication method (protocol) (b5)
0: TCP/IP
1: UDP/IP
(3) Opening method (b10 and b11)
00: Active open or UDP/IP
10: Unpassive open
11: Fullpassive open
Left User
b15 b8
0 (1) 0
b0
……
b15 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
0 (7)(8)
b0
(1)
(2)0(3)(6) (5) (4)
b15 b12 b11 b10 b9 b6 b5 b4 b3 b2
0000(3)
b0
……
(1)(2)