17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
17.2 Remote STOP
The following figure shows the RSTOP instruction execution timing.
If the J.RSTOP, G.RSTOP, or Z.RSTOP is used to execute processing, processing of one time is successively followed by
the next processing while the start-up contact is on.
If the JP.RSTOP, GP.RSTOP, or ZP.RSTOP is used to execute processing, processing is executed once at the start-up
contact off-to-on rise.
When completed successfully
Depending on the system configuration and sequence scan time, several scans may be required until the sequence scan STOP completes.
When completed with an error
END0END0END0END0END0
OFF OFF
OFF
ON
ON
OFF
RSTOP
END0END0
OFF
1 scan
Sequence scan
Start contact
Completion device (d)
Completion status
indication device (d)+1
Channel n
CPU module on
the own station
CPU module on
the target station
Network module
CC-Link IE
Controller
Network module
Remote STOP
Stopped
Sequence scan
END0END0END0END0END0
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
RSTOP
1 scan
Error code
Sequence scan
Start contact
Completion device (d)
Completion status
indication device (d)+1
Channel n
Target station error
CPU module on
the own station
CC-Link IE
Controller
Network module
Link dedicated
instructions processing
result CH1 (SW0030)