17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
17.3 Reading Clock Data from the Programmable Controller on Another Station
Clock data
Processing details
Clock data is read from the target station CPU module. The target station is specified with the target network number (J) or
the start I/O number (U) of the own station or node and the target station number (s2). After completion of request to the
target station, the completion device specified by (d2) turns on.
The specifiable stations are those with the specified network number that are included in one of the following networks.
The execution status and the completion status of the RTMRD instruction can be checked with the completion device (d2)
and the completion status indication device (d2)+1.
Operand: (d1)
Device Item Description Setting range Set by
+0 Clock data Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Month (01H to 12H)
The range of the 4 digits of the year is 1980 to 2079.
System
+1 Upper 8 bits: Day (01H to 31H)
Lower 8 bits: Hour (00H to 23H)
System
+2 Upper 8 bits: Minute (00H to 59H)
Lower 8 bits: Second (00H to 59H)
System
+3 Upper 8 bits: Year (19H and 20H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
The range of the 4 digits of the year is 1980 to 2079.
System
CH: Channel
MELSECNET/H
MELSECNET/10
CC-Link IE Controller Network
CC-Link IE Field Network
Ethernet
Completion device (d2)
This device turns on during END processing of the scan where the RTMRD instruction completes, and turns off during the next END processing.
Completion status indication device (d2)+1
This device turns on or off depending on the completion status of the RTMRD instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the RTMRD instruction completes, and turns off during the next
END processing.
(d1)
RTMRD
CH8
CHn
CH1
CC-Link IE Controller
Network moduleCPU module CPU module Network module
[Own station] [Target station]
Clock data