1592
17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
17.4 Writing Clock Data to the Programmable Controller on Another Station
■Description, range, data type
*1 If the instruction is executed with group or all stations specification:
For the target station CPU type, specify either 0000H or 03FFH. If the target station is in CC-Link IE Field Network, group specification is
not available. To check that the data has been written successfully in the target station, examine whether the CPU module of the
destination has entered the RUN state.
*2 If the instruction is executed with the control system CPU (03D0H) or standby system CPU (03D1H) specified, it may complete with an
error if system switching occurs in the target station (error code: 4244H, 4248H).
Retry to execute the instruction if it completed with an error due to the above error.
Operand Description Range Data type Data type (label)
(J/U) J(P).RTMWR (J): Target station network number 1 to 239 16-bit unsigned binary ANY16
G(P).RTMWR (U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own node
00H to FEH 16-bit unsigned binary ANY16
Z(P).RTMWR (J): Target station network number 1 to 239 String ANY16_OR_STRING_
SINGLE
Z(P).RTMWR (U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own node
00H to FEH String ANY16_OR_STRING_
SINGLE
(s1) Own station channel ( Page 1450 Range of available
channel numbers)
1 to 8, 11 to 18 16-bit unsigned binary ANY16
(s2) Specify the station number of the target station/target node.
(1) Station number specification
1 to 120
(2) Group specification
*1
81H to A0H: All stations of group numbers 1 to 32
(3) All-station specification
*1
FFH: All stations of target network numbers, except own
station
1 to 120
81H to A0H
FFH
16-bit unsigned binary ANY16
(s3) Specify that CPU module in the target station that is to be
accessed.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
*2
• 03D1H: Addressed to standby system CPU
*2
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
0000H
03D0H to 03D3H
03E0H to 03E3H
03FFH
16-bit unsigned binary ANY16
(s4) Own station start device containing the clock data to be written Device name ANY16_ARRAY
(Number of elements: 5)
(d) Device of the own station, which turns on for one scan upon
completion of the instruction.
When the instruction completes with an error, (d)+1 also turns
on.
Bit ANYBIT_ARRAY
(Number of elements: 2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL