18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.2 Writing Data to the Intelligent Device Station/Remote Device Station (16-bit Address Specified)
1609
18
For the REMTO instruction, the number of resends and the response wait timer can be set in the following link
special register (SW) areas.
• Number of resends (REMFR/REMTO) (SW001A)
• Response wait timer (REMFR/REMTO) (SW001B)
If the number of resends (SW001A) is set, the REMTO instruction completes with an error after the following
time has elapsed:
(Number of resends (REMFR/REMTO) + 1) Response wait timer (REMFR/REMTO)
Note, however, that no retry is performed if the target station is disconnected. If the REMTO instruction
completes with an error, execute the instruction again after the target station returns to the system.
Error code (SW0080
to SW009F)
Description
4000H to 4FFFH MELSEC iQ-R CPU Module User's Manual (Application)
D000H to DFFFH MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)