18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.7 Setting Parameters
1629
18
18.7 Setting Parameters
G(P).CCPASET
These instructions set the parameters in the CC-Link IE Field Network master and local modules.
Execution condition
Setting data
Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Ladder ST
ENO:=G_CCPASET(EN,U,s1,s2,s3,s4,d);
ENO:=GP_CCPASET(EN,U,s1,s2,s3,s4,d);
FBD/LD
Instruction Execution condition
G.CCPASET
GP.CCPASET
Operand Description Range Data type Data type (label)
(U) Start I/O number (first three digits in four-digit hexadecimal
representation) of own station or own node
00H to FEH 16-bit unsigned binary ANY16
(s1) Own station start device where control data is stored Refer to the control data. Device name ANY16
*1
(s2) Own station start device containing the network
configuration settings
Device name ANY16
*1
(s3) Own station start device containing the reserved station
specification
Device name ANY16
*1
(s4) Own station start device containing the error invalid station
setting
Device name ANY16
*1
(d) Device of the own station, which turns on for one scan upon
completion of the instruction.
When the instruction completes with an error, (d)+1 also
turns on.
Bit ANYBIT_ARRAY
(Number of elements:
2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(U) (s1) (s2) (s3) (s4)
(d)
EN ENO
U
s1
d
s2
s3
s4