1630
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.7 Setting Parameters
■Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■Control data
Operand Bit Word Double word Indirect
specification
Constant Others
(U)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(U)
(s1)
*2
(s2)
*2
(s3)
*2
(s4)
*2
(d)
*1
*3
Operand: (s1)
Device Item Description Setting range
*1
Set by
+0 Completion status The instruction completion status is stored.
•0: Normal
• Other than 0: Error (error code)
System
+1 Setting flag Specifies whether the setting data in (s2) to (s4) are valid/invalid
(1) Presence of network configuration setting data (bit 0)
• 0: Invalid
*2
• 1: Valid
(2) Presence of reserved station setting data (bit 1)
• 0: Invalid
*2
• 1: Valid
(3) Presence of error invalid station setting data (bit 2)
• 0: Invalid
*2
• 1: Valid
(4) Presence of submaster function (bit 3)
• 0: Invalid
*2
• 1: Valid
(5) Presence of IP packet transfer function (bits 4, 5)
• 00: Invalid
• 01: Valid
(6) Data link faulty station setting (bit 8)
• 0: Cleared
• 1: Held
(7) CPU STOP time output setting (bit 9)
• 0: Held
• 1: Cleared
(8) Link scan mode (bit 10)
• 0: Sequence scan unsynchronized
• 1: Sequence scan synchronized
(9) Network topology setting (bit 11)
• 0: Line topology, star topology, or mixed topology of line and star
• 1: Ring topology
(10)CPU error time output setting (bit 12)
• 0: Cleared
• 1: Held
(11)Master station return time operation setting (bit 13)
Enabled only when the station type is master.
• 0: Returning as the master operating station
• 1: Returning as the submaster operating station
(12)Submaster setting (bit 14)
Enabled only when the station type is submaster.
• 0: Operating with the parameters of the master station
• 1: Operating with the parameters of the own, or submaster, station
Left User
+2 Total number of slave
stations
Sets the total number of slave stations connected. 1 to 121
*3
User
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0 (12) (11)
(10)
(9) (8) (7) (6) 0 (5) (4) (3) (2) (1)