18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.7 Setting Parameters
1633
18
■Error invalid station setting data (for master station setting only)
*1 Make the setting for the station number that was set with the appropriate setting information setting data.
If both the error invalid and reserved stations are specified for the same station, the reserved station setting will take priority.
Any station numbers outside the range specified by the number of slave stations or other than those specified
in the individual station information settings are ignored even if they are specified as reserved stations or
temporary error invalid stations.
• This instruction sets the parameters in the CC-Link IE Field Network master and local modules.
• The execution status and the completion status of the G(P).CCPASET instruction can be checked with the completion
device (d) and the completion status indication device (d)+1.
Operand: (s4)
Device Item Description Setting range Set by
+0 to +7 Station 1 to 120
specification
*1
Specify the error invalid station.
• 0: Not specified
• 1: Specified
Each number in the table indicates a station number.
The default parameter specifies that all stations are 0 (not specified).
Left User
• Completion device (d)
This device turns on during END processing of the scan where the G(P).CCPASET instruction completes, and turns off during the next END processing.
• Completion status indication device (d)+1
This device turns on or off depending on the completion status of the G(P).CCPASET instruction.
When completed successfully: The device remains off.
When completed with an error: The device turns on during END processing of the scan where the G(P).CCPASET instruction completes, and turns off during
the next END processing.
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
(s4)+0
(s4)+1
(s4)+2
(s4)+3
(s4)+4
(s4)+5
(s4)+6
(s4)+7
CCPASET
CC-Link IE Field Network
master/local moduleCPU module
[Own station]
Setting parameters