20 SERIAL COMMUNICATION INSTRUCTIONS
20.6 Receiving Data Using the Bidirectional Protocol
1693
20
• The following table summarizes the processes that take place if another instruction is issued while the G(P).BIDIN
instruction is active or the G(P).BIDIN instruction is issued while another instruction is active with the same channel.
*2 The following instructions are not available with the same channel as for the G(P).BIDIN instruction because they use a communication
protocol different from the one used by this instruction. In addition, if these are used with the same channel as for the G(P).BIDIN
instruction, a communication protocol setting error (7FF2H) will occur.
Instruction to execute
concurrently
*2
Possibility of
concurrent execution
Handling for concurrent execution
G(P).BIDOUT
G(P).BIDIN The instruction is ignored and does not start processing until the active instruction
completes.
Concurrent execution is, however, possible if they use different channels.
ZP.CSET A dedicated instruction concurrent execution error (7FF0H) occurs in the second
instruction.
Concurrent execution is, however, possible if they use different channels.
G(P).PUTE
G(P).GETE
Z.BUFRCVS Concurrent execution of the G(P).BIDIN and Z.BUFRCVS instructions is not possible.
Concurrent execution is, however, possible if they use different channels.
G(P).SPBUSY
ZP.UINI A dedicated instruction concurrent execution error (7FF0H) occurs in the second
instruction.
• G(P).ONDEMAND, G(P).CPRTCL, G(P).OUTPUT, G.INPUT, and G(P).PRR instructions
Error code
((s)+1)
Description
7000H to 7FFFH MELSEC iQ-R Serial Communication Module User's Manual (Application)