1764
21 A/D CONVERSION INSTRUCTIONS
21.3 Restoring the User Range Setting Values
• Program example
In the following cases, execution of the G(P).OGSTOR instruction results in an error.
• The module has been set as a target of synchronization.
• The simultaneous conversion mode has been selected on the high speed analog-digital converter module.
• The wave output mode has been selected on the D/A converter module.
In the following case, execution of the G(P).OGSTOR instruction will be disabled.
• The high-speed output mode has been selected on the high speed digital-analog converter module.
(14) Set control data.
(31) Restore the offset/gain settings.
Error code
((s)+1)
Description
1860H In the following cases, the G(P).OGSTOR instruction will be being executed.
• During offset/gain setting module
• Has been set as a target of module-to-module synchronization.
• During simultaneous conversion mode (R60ADH4)
• During wave output mode (D/A converter module)
1861H The G(P).OGSTOR instruction is being executed consecutively.
1862H The G(P).OGSTOR instruction is being executed for a model different from that for which the G(P).OGLOAD instruction has been
executed.
The G(P).OGSTOR instruction is being executed before the G(P).OGLOAD instruction is executed.
1863H The value set in the save data type setting 1 (S)+2 or the save data type setting 2 (s)+3 is out of the valid range.