7 APPLICATION INSTRUCTIONS
7.6 Reading/Writing Data Instructions
621
7
*1 The set value is from 00000000H to FFFFFFFEH (from the beginning of the file) or FFFFFFFFH (added to the end of the file).
Writing
data after
converted
to CSV
format
0100H: Decimal (signed 16-
bit data)
0: Word Word (1 to 65535) Head/end
*1
Word
1: Byte Word (1 to 65535) Head/end
*1
Byte
2: Unit of the data type
specified by the
execution/completion
type
Word (1 to 65535) Head/end
*1
Word
0101H: Decimal (unsigned
16-bit data)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Word (1 to 65535) Head/end
*1
Word
0110H: Decimal (signed 32-
bit data)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Double word (1 to 32767) Head/end
*1
Double word
0111H: Decimal (unsigned
32-bit data)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Double word (1 to 32767) Head/end
*1
Double word
0120H: Hexadecimal (16-bit
data)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Word (1 to 65535) Head/end
*1
Word
0121H: Hexadecimal (32-bit
data)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Double word (1 to 32767) Head/end
*1
Double word
0130H: String (ASCII data) 0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Number of elements (1 to
1023)
Head/end
*1
Number of elements
0140H: Floating point real
number (single-precision real
number)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
Double word (1 to 32767) Head/end
*1
Double word
0141H: Floating point real
number (double-precision
real number)
0: Word
1: Byte
(Cannot be specified)
2: Unit of the data type
specified by the
execution/completion
type
4 words (1 to 16383) Head/end
*1
4 words
Execution/completion type
(d1)+0
Data type
specification
(d1)+7
Processing unit and setting range
Number of request
write data
(s3)+0
File position
(d1)+4, (d1)+5
Number of data
actually written
(d1)+2