7 APPLICATION INSTRUCTIONS
7.20 Data Processing Instructions
927
7
Processing details
These instructions search the (n) points of 16-bit binary data in the device specified by (s) for the minimum value, and store
the minimum value in the device specified by (d). Each instruction searches data starting from the device specified by (s)
and detects first the minimum value in the xth point from (s), and stores x in (d)+1 and the number of minimum values in
(d)+2.
Operation error
There is no operation error.
(d) Minimum value
(d)+1: Location
(d)+2: Number of minimum values

5015 (BIN)
6192 (BIN)
5571 (BIN)
5015 (BIN)
5571 (BIN)
(n)
(s)
(s)+1
(s)+(n)-2
(s)+(n)-1
(s)+2
5015 (BIN)
1
2
(d)
(d)+1
(d)+2