7.21 Database Access Instructions
*1 Use 16 or less fields/tables for a programmable controller CPU with firmware version earlier than "28".
2025H The database cannot be recognized. Or recovery of the database
failed.
Check the status of the SD memory card.
If the error database check file (2:\CPUDB\ErrorDB.txt) exists and it
lists a database which resides under the CPUDB folder or its
subfolder, delete the database with its folder and then create a new
database.
If the problem persists after powering off and on the CPU module or
reset it, or the error database check file (2:\CPUDB\ErrorDB.txt)
exists and it lists a database which resides under other than the
CPUDB folder or its subfolder, delete the dbmaintainpath.txt file on
the $MELPRJ$\$DBASYS$ folder in the SD memory card, delete all
database folders (excluding the CPUDB folder), and then create a
new database using the DBIMPORT(P) instruction.
Others The character code of the Unicode text file is incorrect.
The database to be accessed is in an invalid status.
Check the character code of the Unicode text file.
If the same error occurs even after powering off and on or reset the
CPU module, delete the access-target database folder, and create a
new database by using the DBIMPORT(P) instruction.