100
4 SAFETY FB SPECIFICATIONS
4.14 M+SF_TSSEN_R
8012 ESPE Interrupted 2 The FB has detected a safety demand from the sensor at
the status 8000H or 8013H.
The switch was automatically tested.
• o_bReady: ON
• o_bS_OSSD_Out: OFF
• o_bS_TestOut: ON
• o_bTestPossible: OFF
• o_bTestExecuted: ON
• o_bError: OFF
Reset the safety demand for the connected
safeguard by resetting the interruption of the
sensors. Check a failure or an error of the
sensor.
8013 Wait for Reset 2 Wait for rising trigger of i_bReset after state 8012H.
• o_bReady: ON
• o_bS_OSSD_Out: OFF
• o_bS_TestOut: ON
• o_bTestPossible: OFF
• o_bTestExecuted: ON
• o_bError: OFF
Set i_bReset to ON.
Please do the above actions when the FB detects an error or is in an unexpected state. However, when the situation is still not corrected, please check the
following.
• A failure in safety devices and emergency stop devices
• Wiring and status of a safety remote I/O module and a safety programmable controller
• Programming logic, the memory allocation of safety devices, and the connections of safety FB variables
• Setting of i_bS_StartReset and i_bS_AutoReset
o_wDiagCode
(Hexadecimal)
State name Description, output setting Action
WARNING