170
APPX
Appendix 5 How to Use MELSEC-Q Series Modules
Engineering tool
The version of an engineering tool that supports the MELSECNET/H network module is restricted. ( MELSEC iQ-R
CPU Module User's Manual (Application))
When the module occupying two slots (QJ71LP21S-25) is mounted, it is displayed on an engineering tool as occupying one
slot. Therefore, when setting the module on "Module Configuration", mount the blank cover module (QG60) on the left side
of the QJ71LP21S-25 mounted slot to secure an empty space of one slot (16 points). Then, set the empty space of one slot
(16 points) in "I/O Assignment Setting" in the [I/O Assignment] tab on the "System Parameter" window.
Data communications from the engineering tool (GX Works3) to other stations (stations where the engineering tool is not
connected) cannot be performed via MELSECNET/H.
On the system monitor and MELSECNET diagnostics of the engineering tool (GX Works3), the mode of the MELSECNET/
H network module is always displayed as "Online".
None of T, C, and ST can be specified for the device set in the link refresh settings. Specify another device.
There are precautions for MELSECNET diagnostics of the engineering tool (GX Works3) via following devices.
GX works2 and GX Developer
From GX Works2 connected to a MELSEC iQ-R series CPU module, access to a MELSEC-Q series or MELSEC-L series
CPU module is possible via the MELSECNET/H network module mounted on the RQ extension base unit. For the access
via a MELSEC iQ-R series CPU module, use GX Works2 with the version of 1.519R or later.
For data access from GX Works2 to other stations via a MELSEC iQ-R series CPU module, a remote password, if it is set,
cannot be canceled from GX Works2. Cancel the password using the engineering tool that supports a MELSEC iQ-R series
CPU module.
From GX Developer, access to other stations via a MELSEC iQ-R series CPU module is not possible.
(1) QJ71LP21S-25 (module occupying two slots)
(2) QG60 (blank cover module)
Device Precaution
CC-Link IE Controller Network interface board Use the SW1DNC-MNETG-B with version 1.22Y or later and the ROM with version 2T or
later.
CC-Link IE Field Network interface board Use the SW1DNC-CCIEF-B with version 1.10L or later.
GOT MELSECNET diagnostics cannot be used If the engineering tool (GX Works3) is
connected to the programmable controller using the FA transparent function of GOT (in a
CC-Link IE Controller Network or a CC-Link IE Field Network connection).
(2) (1)