Appendix 6 EMC and Low Voltage Directives
173
A
EMC Directive related standards
■ Emission requirements
Standard: EN61131-2:2007
*1 QP: Quasi-Peak value, Mean: Average value
*2 Programmable controller is an open-type device and must be placed in a conductive control panel or similar type of enclosure. The tests
were conducted with the programmable controller installed in a control panel, applying the maximum rated input voltage of the power
supply module.
■ Immunity requirements
Standard: EN61131-2:2007
*1 Programmable controller is an open-type device and must be placed in a conductive control panel or similar type of enclosure. The tests
were conducted with the programmable controller installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporarily vary within 10%.
Test item Test description Value specified in standard
CISPR16-2-3
Radiated emission
*2
The electromagnetic wave emitted by
the product to the external space is
measured.
• 30 to 230MHzQP: 40dBV/m (measured at 10m distance)
*1
• 230 to 1000MHzQP: 47dBV/m (measured at 10m distance)
CISPR16-2-1, CISPR16-1-2
Conducted emission
*2
The noise level which the product
emits to the power line is measured.
• 0.15 to 0.5MHzQP: 79dB, Mean: 66dB
*1
• 0.5 to 30MHzQP: 73dB, Mean: 60dB
Test item Test description Value specified in standard
EN61000-4-2
Electrostatic discharge immunity
*1
An electrostatic discharge is applied
to the enclosure of the equipment.
• 8kV: Air discharge
• 4kV: Contact discharge
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
*1
An electric field is radiated to the
product.
80% AM modulation @1kHz
• 80 to 1000MHz: 10Vm
• 1.4 to 2.0GHz: 3Vm
• 2.0 to 2.7GHz: 1Vm
EN61000-4-4
Fast transient burst immunity
*1
Burst noise is applied to power lines
and signal lines.
• AC/DC power, I/O power, and AC I/O (unshielded) lines: 2kV
• DC I/O, analog, and communication lines: 1kV
EN61000-4-5
Surge immunity
*1
Lightning surge is applied to power
lines and signal lines.
• AC power, AC I/O power, and AC I/O (unshielded) lines: 2kV CM, 1kV DM
• DC power and DC I/O power lines: 0.5kV CM, 0.5kV DM
• DC I/O, AC I/O (shielded), analog
*2
, and communication lines: 1kV CM
EN61000-4-6
Conducted RF immunity
*1
High-frequency noise is applied to
power lines and signal lines.
0.15 to 80MHz,
80% AM modulation @1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic field
immunity
*1
The product is immersed in the
magnetic field of an induction coil.
50/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruptions
immunity
*1
Power voltage is momentarily
interrupted.
• 0%, 0.5 periods, starting at zerocrossing
• 0%, 250/300 periods (50/60Hz)
• 40%, 10/12 periods (50/60Hz)
• 70%, 25/30 periods (50/60Hz)