1 SYSTEM CONFIGURATION
1.4 Precautions for System Configuration
63
1
Precautions for C Controller system configuration
Pay attention to the following when configuring a C Controller system by using a C Controller module.
When using MELSEC iQ-R series modules
The following describes the precautions when using MELSEC iQ-R series modules.
CC-Link IE Controller Network module
The module cannot be used as a relay station for the interlink transmission function or the routing functions. To use either of
those functions, use a CC-Link IE Controller Network module controlled by a programmable controller CPU as a relay
station.
An interrupt sequence program cannot be started.
The dynamic routing function cannot be used.
The IP packet transfer function using the Ethernet port of C Controller module are not available.
CC-Link IE Field Network master/local module
The module cannot be used as a relay station for the interlink transmission function or the routing functions. To use either of
those functions, use a CC-Link IE Field Network master/local module controlled by a programmable controller CPU as a
relay station.
An interrupt sequence program cannot be started.
It cannot be used as a submaster station.
The dynamic routing function cannot be used.
The IP packet transfer function using the Ethernet port of C Controller module are not available.
The high-speed remote net of communication mode cannot be used.
CC-Link module
An interrupt sequence program cannot be started.
The automatic CC-Link start function cannot be used.
The standby master function cannot be used.
The remote I/O net mode cannot be used.
The master station duplex function cannot be used.
The station-based block data assurance cannot be used.
Serial communication module
Only the nonprocedural protocol can be used.
Ethernet interface module with built-in CC-Link IE
The Ethernet function cannot be used.
When using MELSEC-Q series modules
The following describes the precautions when using MELSEC-Q series modules.
FL-net (OPCN-2) interface module
The word block read/write request messages using the message transmission function cannot be received.
The auto refresh function cannot be used.
MELSECNET/H network module
Remote I/O net cannot be used.
The module cannot be used as a relay station for the interlink data transmission function or the routing functions. To use
either of those functions, use a MELSECNET/H network module controlled by a programmable controller CPU as a relay
station.
An interrupt sequence program cannot be started.
The network diagnostic function cannot be used.
The module cannot be used in the simple dual-structured system.
The debug mode cannot be set.