2 DETAILS OF THE FB LIBRARY
2.6 M+ArrayHandling_Sort_R
37
2
Performance value
The following table lists the performance values of this FB under the following conditions.
CPU module: R04CPU
File register storage location: Extended SRAM cassette
FB compilation method: Subroutine type
*1 The time required from start to end of the processing
Restrictions and precautions (1) This FB does not include the error recovery processing. Prepare the error recovery processing separately to suit the
user's system and the expected operation.
(2) This FB uses the long index register LZ0 and LZ1. When using an interrupt program, do not use the corresponding
index register.
(3) The FB cannot be used in an interrupt program.
(4) Using the FB in a program that is to be executed only once, such as a subroutine program or a FOR-NEXT loop, has a
problem that i_bEN (execution command) can no longer be turned off and normal operation is not possible; Always use
the FB in a program that is capable of turning off the execution command.
(5) The FB requires the configuration of the ladder for every input label.
(6) In this FB, the same address cannot be set for i_udInAryAddr (input array data start address) and i_udOutAryAddr
(output array data start address).
Input label Time required for the
processing
*1
Maximum scan time Number of the scans
required for the
processing
Number of data points Data type selection
10000 points 0: Word [signed] 557ms 7.29ms 93 scans
1: Double Word [signed] 792ms 10.3ms 93 scans
2: Single-precision real number 816ms 10.3ms 101 scans
3: Word [unsigned] 557ms 7.34ms 93 scans
4: Double Word [unsigned] 792ms 10.2ms 93 scans
500000 points 0: Word [signed] 40400ms 9.08ms 6623 scans
1: Double Word [signed] 57500ms 10.4ms 6636 scans
2: Single-precision real number 58700ms 10.7ms 7007 scans
3: Word [unsigned] 40400ms 9.06ms 6623 scans
4: Double Word [unsigned] 57500ms 10.4ms 6636 scans
1000000 points 0: Word [signed] 85300ms 9.07ms 13993 scans
1: Double Word [signed] 122000ms 10.3ms 14025 scans
2: Single-precision real number 124000ms 10.4ms 14766 scans
3: Word [unsigned] 85300ms 9.07ms 13993 scans
4: Double Word [unsigned] 122000ms 10.3ms 14025 scans