5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected
165
5
Network configuration settings
Set the number of link device points and assignment of slave stations to the master station. If selecting "Local Station" in
"Required Settings", setting is not possible.
Operating procedure
1. Select a module from "Module List", and drag and drop it to the list of stations or the network map.
2. Select and input parameters as shown below.
3. Select "Close with Reflecting the Setting" and complete "Network Configuration Settings". If the window is closed using
the [] button, the settings are not reflected.
Window
Displayed items
Item Description
Assignment Method Number of points or Start number
Total number of slave
stations
2
Item Range/value
CCIEF programmable controller
Master (1-0)
CCIEF programmable controller
Local (1-1)
CCIEF programmable controller
Local (1-2)
Model RJ71GF11-T2 RJ71GF11-T2 RJ71GF11-T2
STA# 0 1 2
Station Type Master Station Local station Local station
RX/RY Points: (Unavailable)
Start: (Unavailable)
End: (Unavailable)
Points: 32
Start: 0060
End: 007F
Points: 32
Start: 0080
End: 009F
RWr/RWw Points: (Unavailable)
Start: (Unavailable)
End: (Unavailable)
Points: 16
Start: 0030
End: 003F
Points: 16
Start: 0040
End: 004F
Reserved/Error Invalid
Station
No Setting No Setting No Setting
Network synchronous
communication
Asynchronous Asynchronous Asynchronous
Drag and drop a module.
List of stations
Network map